Feasibility of burning refuse derived fuel in institutional size oil-fired boilers. Final report [electronic resource].
- Published
- Washington, D.C. : United States. Dept. of Energy, 1980.
Oak Ridge, Tenn. : Distributed by the Office of Scientific and Technical Information, U.S. Dept. of Energy. - Physical Description
- Pages: 78 : digital, PDF file
- Additional Creators
- United States. Department of Energy and United States. Department of Energy. Office of Scientific and Technical Information
Access Online
- Restrictions on Access
- Free-to-read Unrestricted online access
- Summary
- This study investigates the feasibility of retrofitting existing oil-fired boilers of institutional size, approximately 3.63 to 36.3 Mg steam/h (8000 to 80,000 lbs steam/h) for co-firing with refuse-derived fuel (RDF). Relevant quantities describing mixtures of oil and RDF and combustion products for various levels of excess air are computed. Savings to be realized from the use of RDF are derived under several assumptions and allowable costs for a retrofit are estimated. An extensive survey of manufacturers of burners, boilers, and combustion systems showed that no hardware or proven design is yet available for such retrofit. Approaches with significant promises are outlined: the slagging burner, and a dry ash double vortex burner for low heat input from RDF. These two systems, and an evaluation of a small separate RDF dedicated combustor in support of the oil-fired boiler, are recommended as topics for future study.
- Report Numbers
- E 1.99:doe/cs/20167-03
doe/cs/20167-03 - Subject(s)
- Other Subject(s)
- Note
- Published through SciTech Connect.
10/01/1980.
"doe/cs/20167-03"
National Center for Resource Recovery, Inc., Washington, DC (USA) - Funding Information
- AC01-76CS20167
View MARC record | catkey: 13819695