Actions for Report on Transport and Loading of Explosives in the Femtosecond Tank, Room 1711A HEAF 00-010 [electronic resource].
Report on Transport and Loading of Explosives in the Femtosecond Tank, Room 1711A HEAF 00-010 [electronic resource].
- Published
- Washington, D.C. : United States. Dept. of Energy, 2002.
Oak Ridge, Tenn. : Distributed by the Office of Scientific and Technical Information, U.S. Dept. of Energy. - Physical Description
- 8p : digital, PDF file
- Additional Creators
- Lawrence Berkeley National Laboratory, United States. Department of Energy, and United States. Department of Energy. Office of Scientific and Technical Information
Access Online
- Restrictions on Access
- Free-to-read Unrestricted online access
- Summary
- The current OSP associated with Room 1711A located in Building 191 (HEAF) sets a limit of 5 grams Net Explosive Weight (NEW) of explosives for the room. A question was raised as to the capability of that room to withstand the overpressure created by a detonation of 5 grams NEW of explosives. Calculations were inconclusive, but indicated the wallboard would not remain intact if there was a detonation of 5 grams NEW at a distance of eight feet from the wall. These calculations did not seem logical. To verify the hypothesis, a series of experiments were conducted in the 1 Kilogram tank. The experiments consisted of exposing a pre-built double-sided wall with the same stud spacing and drywall thickness found in the walls of Room 1711A to various amounts of explosives to create expected overpressures. The objective of this test was to prove or disprove that the walls in room 1711A could withstand a detonation of 5 grams of high explosives and to determine if larger quantities of explosives could be worked on in the room while still providing the required level of protection for personnel outside the room. Testing has verified that not only can the walls withstand a 5 gram explosion, but a 10.75 gram explosion as well. A second test was conducted using 20 grams of explosive plus a detonator. Although the inner piece of drywall cracked, the outer piece of drywall maintained its integrity, thereby confining the effects of the anticipated overpressure to the room.
- Report Numbers
- E 1.99:ucrl-id-148142
ucrl-id-148142 - Subject(s)
- Other Subject(s)
- Note
- Published through SciTech Connect.
04/25/2002.
"ucrl-id-148142"
Hill, D L. - Funding Information
- W-7405-ENG-48
View MARC record | catkey: 14106761