Actions for Modeling particle loss in ventilation ducts [electronic resource].
Modeling particle loss in ventilation ducts [electronic resource].
- Published
- Washington, D.C. : United States. Dept. of Energy, 2003.
Oak Ridge, Tenn. : Distributed by the Office of Scientific and Technical Information, U.S. Dept. of Energy. - Additional Creators
- United States. Department of Energy and United States. Department of Energy. Office of Scientific and Technical Information
Access Online
- Restrictions on Access
- Free-to-read Unrestricted online access
- Summary
- Empirical equations were developed and applied to predict losses of 0.01-100 {micro}m airborne particles making a single pass through 120 different ventilation duct runs typical of those found in mid-sized office buildings. For all duct runs, losses were negligible for submicron particles and nearly complete for particles larger than 50 {micro}m. The 50th percentile cut-point diameters were 15 {micro}m in supply runs and 25 {micro}m in return runs. Losses in supply duct runs were higher than in return duct runs, mostly because internal insulation was present in portions of supply duct runs, but absent from return duct runs. Single-pass equations for particle loss in duct runs were combined with models for predicting ventilation system filtration efficiency and particle deposition to indoor surfaces to evaluate the fates of particles of indoor and outdoor origin in an archetypal mechanically ventilated building. Results suggest that duct losses are a minor influence for determining indoor concentrations for most particle sizes. Losses in ducts were of a comparable magnitude to indoor surface losses for most particle sizes. For outdoor air drawn into an unfiltered ventilation system, most particles smaller than 1 {micro}m are exhausted from the building. Large particles deposit within the building, mostly in supply ducts or on indoor surfaces. When filters are present, most particles are either filtered or exhausted. The fates of particles generated indoors follow similar trends as outdoor particles drawn into the building.
- Report Numbers
- E 1.99:lbnl--52449
lbnl--52449 - Other Subject(s)
- Note
- Published through SciTech Connect.
04/01/2003.
"lbnl--52449"
": NN2004000"
Atmospheric Environment 37 39-40 ISSN 0004-6981; ATENBP FT
Nazaroff, William W.; Sippola, Mark R.
Ernest Orlando Lawrence Berkeley NationalLaboratory, Berkeley, CA (US) - Funding Information
- DE-AC02-05CH11231
470901
View MARC record | catkey: 14133130