Actions for Functional issues and environmental qualification of digital protection systems of advanced light-water nuclear reactors [electronic resource].
Functional issues and environmental qualification of digital protection systems of advanced light-water nuclear reactors [electronic resource].
- Published
- Rockville, Md. : U.S. Nuclear Regulatory Commission, 1994.
Oak Ridge, Tenn. : Distributed by the Office of Scientific and Technical Information, U.S. Dept. of Energy. - Physical Description
- 71 pages : digital, PDF file
- Additional Creators
- U.S. Nuclear Regulatory Commission and United States. Department of Energy. Office of Scientific and Technical Information
Access Online
- Restrictions on Access
- Free-to-read Unrestricted online access
- Summary
- Issues of obsolescence and lack of infrastructural support in (analog) spare parts, coupled with the potential benefits of digital systems, are driving the nuclear industry to retrofit analog instrumentation and control (I&C) systems with digital and microprocessor-based systems. While these technologies have several advantages, their application to safety-related systems in nuclear power plants raises key issues relating to the systems` environmental qualification and functional reliability. To bound the problem of new I&C system functionality and qualification, the authors focused this study on protection systems proposed for use in ALWRs. Specifically, both functional and environmental qualification issues for ALWR protection system I&C were addressed by developing an environmental, functional, and aging data template for a protection division of each proposed ALWR design. By using information provided by manufacturers, environmental conditions and stressors to which I&C equipment in reactor protection divisions may be subjected were identified. The resulting data were then compared to a similar template for an instrument string typically found in an analog protection division of a present-day nuclear power plant. The authors also identified fiber-optic transmission systems as technologies that are relatively new to the nuclear power plant environment and examined the failure modes and age-related degradation mechanisms of fiber-optic components and systems. One reason for the exercise of caution in the introduction of software into safety-critical systems is the potential for common-cause failure due to the software. This study, however, approaches the functionality problem from a systems point of view. System malfunction scenarios are postulated to illustrate the fact that, when dealing with the performance of the overall integrated system, the real issues are functionality and fault tolerance, not hardware vs. software.
- Report Numbers
- E 1.99:nureg/cr--5904
E 1.99: ornl/tm--12164
ornl/tm--12164
nureg/cr--5904 - Subject(s)
- Other Subject(s)
- Note
- Published through SciTech Connect.
04/01/1994.
"nureg/cr--5904"
" ornl/tm--12164"
"TI94011799"
Wood, R.T.; Clark, R.L.; Korsah, K. - Type of Report and Period Covered Note
- Topical; 04/01/1994 - 04/01/1994
- Funding Information
- AC05-84OR21400
View MARC record | catkey: 14365807