Potassium Rankine cycle vapor chamber (heat pipe) radiator study
- Author:
- Killen, R. E.
- Published:
- Sep 1, 1971.
- Physical Description:
- 1 electronic document
- Additional Creators:
- Gerrels, E. E.
- Access Online:
- hdl.handle.net
- Restrictions on Access:
- Unclassified, Unlimited, Publicly available.
- Summary:
- A structurally integrated vapor chamber fin (heat pipe) radiator is defined and evaluated as a potential candidate for rejecting waste heat from the potassium Rankine cycle powerplant. Several vapor chamber fin geometries, using stainless steel construction, are evaluated and an optimum is selected. A comparison is made with an operationally equivalent conduction fin radiator. Both radiators employ NaK-78 in the primary coolant loop. In addition, the Vapor Chamber Fin (VCF) radiator utilizes sodium in the vapor chambers. Preliminary designs are developed for the conduction fin and VCF concepts. Performance tests on a single vapor chamber were conducted to verify the VCF design. A comparison shows the conduction fin radiator easier to fabricate, but heavier in weight, particularly as meteoroid protection requirements become more stringent. While the analysis was performed assuming the potassium Rankine cycle powerplant, the results are equally applicable to any system radiating heat to space in the 900 to 1400 F temperature range.
- Collection:
- NASA Technical Reports Server (NTRS) Collection.
- Note:
- Document ID: 19720004957.
Accession ID: 72N12606.
NASA-CR-1866.
GESP-7047. - Terms of Use and Reproduction: